Viessmann Boiler: Convert fuel type from natural gas to liquid propane

Updated · by Aurora Star Tech Inc.

Convert fuel type from natural gas to liquid propane on a Viessmann boiler: Field conversion of both gas valves and coding for LPG operation.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

How to fix convert fuel type from natural gas to liquid propane: step by step

  1. Set adjusting screw A at the gas valve to 2 with a 2.5 mm hex key.
  2. Switch ON/OFF switch 8 to ON by sliding the black control cover outward.
  3. Enter coding level 2 and select 'General'.
  4. Set coding address 11 to 9.
  5. Set coding address 82 to 1 for liquid propane.
  6. Return to coding address 11 and set any value except 9.
  7. Exit coding level 2 and open the gas shut-off valve.
  8. Apply the supplied fuel conversion labels.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977