Viessmann Boiler: Convert fuel type from natural gas to liquid propane gas
Convert fuel type from natural gas to liquid propane gas on a Viessmann boiler: Coding and gas valve change to run the boiler on LPG. The factory setting is natural gas.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix convert fuel type from natural gas to liquid propane gas: step by step
- Set adjusting screw A on the gas valve to "2" using a 2.5 mm hex key.
- Switch the ON/OFF switch "8" to ON. Slide the black control cover outwards to reach it.
- Call up coding level 2 (see page 47).
- Select "General".
- Set coding address 11 to value 9.
- Set coding address 82 to value 1 (liquid propane gas).
- Go back to coding address 11 and select any value except 9.
- Exit coding level 2 and open the gas shut-off valve.
- Apply the supplied fuel conversion labels.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.