Convert from natural gas to liquid propane gas on a Viessmann boiler: The boiler is factory set for natural gas. Coding address 82 is 0 for natural gas. Coding 11 must be set to 9 before 82 can be changed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 19, 28, 35

How to fix convert from natural gas to liquid propane gas: step by step

  1. Set gas valve adjusting screw A to 2 with a 2.5 mm hex key.
  2. Switch the ON/OFF switch 8 to ON. Slide the black control cover out to reach it.
  3. Enter coding level 2 (see page 47).
  4. Open the General group.
  5. Set coding address 11 to 9.
  6. Set coding address 82 to 1 (liquid propane gas).
  7. Return to coding address 11 and select any value except 9.
  8. Exit coding level 2 and open the gas shut-off valve.
  9. Apply the supplied fuel conversion labels.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.