Viessmann Boiler: Convert boiler from natural gas to LPG
Convert boiler from natural gas to LPG on a Viessmann boiler: Field conversion of the gas valve and control settings. Use the fuel conversion kit instructions and label.
Applies to: Vitocrossal 300 CU3A, natural gas to LPG
How to fix convert boiler from natural gas to lpg: step by step
- Set adjusting screw A on the gas valve to "2".
- Turn the ON/OFF switch "8" ON.
- Enter service functions, call up code 2 (General).
- In coding address 11, select value 9.
- In coding address 82, select value 1 (LPG operation).
- Set coding 11 to any value other than 9.
- End service functions.
- Open the gas shut-off valve.
- Apply the fuel conversion label from the kit as shown in its instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.