Viessmann Boiler: Convert boiler from natural gas to liquid propane

Updated · by Aurora Star Tech Inc.

Convert boiler from natural gas to liquid propane on a Viessmann boiler: Factory set to natural gas (coding 82 = 0). Conversion uses coding level 2 and a gas valve adjustment. Fuel conversion labels must be applied.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 45, 60

How to fix convert boiler from natural gas to liquid propane: step by step

  1. Set adjusting screw A at the gas valve to 2 (2.5 mm hex key).
  2. Switch ON/OFF switch 8 to ON. Slide the black control cover outward to reach it.
  3. Enter coding level 2 (see page 47).
  4. Open the General menu.
  5. Set coding address 11 to 9.
  6. Set coding address 82 to 1 (liquid propane gas).
  7. Return to coding address 11 and select any value except 9.
  8. End coding level 2 and open the gas shut-off valve.
  9. Apply the supplied fuel conversion labels.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.