Viessmann Boiler: Connecting Vitodens 200 WB2B with Vitotronic 200 HO1 to the Versatronik 300
Connecting Vitodens 200 WB2B with Vitotronic 200 HO1 to the Versatronik 300 on a Viessmann boiler: Boilers are daisy-chained from control to control with CAT5e cable using RJ45 ends (non-crossover). Plug the cable into the J1 receptacle in the upper right corner of the Versatronik 300 PCB. The cable can be made on site or ordered from Viessmann.
Applies to: Vitodens 200 WB2B with Vitotronic 200 HO1
How to fix connecting vitodens 200 wb2b with vitotronic 200 ho1 to the versatronik 300: step by step
- Plug the CAT5e cable into the J1 receptacle at the upper right of the Versatronik 300 PCB.
- Daisy-chain the cable from control to control, using the LON communication boards on each boiler control.
- Connect the outdoor temperature sensor to the boiler. It can be mounted inside the boiler housing.
- Set the boiler LON and coding addresses as listed in the Vitodens 200 HO1 coding table.
- Make sure no two boiler controls share the same LON address.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control V1.4 manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.