Viessmann Boiler: Connecting the boiler control to a LON system
Connecting the boiler control to a LON system on a Viessmann boiler: Boiler control is linked to Vitotronic 200-H mixing valve controls and a Vitocom LON module. The LON communication module is an accessory and must be installed. Data transfer can take several minutes. Only one Vitotronic can be the fault manager, and each participant number can be used only once in the same LON system.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix connecting the boiler control to a lon system: step by step
- Install the LON communication module (see its installation instructions).
- Set LON participant numbers and functions in coding level 2 (see LON table).
- Set exactly one control as fault manager (code 79:1). All others use 79:0.
- Set the time transmitter and receiver codes (7B:1, 81:3).
- Set the outside temperature transmitter and receiver codes (97:2, 97:1).
- Set LON participant fault monitoring (9C:20) on the mixing valve controls.
- Wait several minutes for the data transfer.
- Run the LON participant check.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 41-42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.