Viessmann Boiler: Connecting control unit power supply
Connecting control unit power supply on a Viessmann boiler: The control must be grounded. L, N and G must not be interchanged. The supply is 120VAC, 1 phase, 60 Hz, 12 A full load.
Applies to: Vitotronic 200-H HK1B, power supply
How to fix connecting control unit power supply: step by step
- Make sure the main supply has overcurrent protection rated at least 12 A and a 2-pole disconnect.
- Provide disconnect means and overcurrent protection as per local codes.
- Connect the supply wire to terminals 11, N and G on the DIN rail inside the junction box.
- Follow the National Electrical Code (NEC) and ANSI/NFPA 70 in the US, or the Canadian Electrical Code (CEC) and CSA C22.1 Part 1 in Canada, plus local codes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.