Viessmann Boiler: Connecting combustion air device (blower and proving switch)
Connecting combustion air device (blower and proving switch) on a Viessmann boiler: Wiring a 120 VAC combustion air blower through the Combustion Air Device Adaptor, with a proving switch.
Applies to: Vitotronic 100 GC1 combustion air blower and proving switch
How to fix connecting combustion air device (blower and proving switch): step by step
- Disconnect power to the control and burners.
- Install the Combustion Air Device Adaptor (PN 7134 563) on the DIN rail inside the connection enclosure, per the adaptor manual.
- Remove the jumper between terminals 16 and 17.
- Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do NOT reverse them.
- Connect the blower to the adaptor as shown: 120 VAC, max 5 FLA, recommended wire AWG 14. Confirm the blower suits the application.
- Wire the proving switch as normally open, rated 120 VAC.
- Provide disconnect means and overcurrent protection as required by local codes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.