Viessmann Boiler: Connecting boiler pumps (shunt, boiler circuit, DHW)
Connecting boiler pumps (shunt, boiler circuit, DHW) on a Viessmann boiler: Pump wiring to the boiler control. Line-voltage pumps are switched through a contactor or motor starter.
Applies to: Vitotronic 100 GC1 boiler control pump outputs
How to fix connecting boiler pumps (shunt, boiler circuit, dhw): step by step
- Use terminals 6-L, 6-G and 6-N in the line voltage connection enclosure for the shunt or boiler circuit pump.
- For a 120 VAC DHW tank pump or shunt pump, use the connection marked B on the connection enclosure.
- For 240 VAC or 3-phase pumps, do not power the pump direct; use a contactor and/or motor starter.
- Select the contactor and connecting wire to suit the pump rating. Contactor activation rating: max 2 FLA. Recommended wire size AWG 14.
- Connect pump and power supply to the contactor, then connect the contactor coil to the corresponding terminals.
- Install pumps per the pump manufacturer's instructions and follow local and national wiring codes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.