Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Connecting a 24 VAC thermostat through a switching relay

Updated · by Aurora Star Tech Inc.

Connecting a 24 VAC thermostat through a switching relay on a Viessmann boiler: Use a switching relay with a normally open, potential-free dry contact (T-T). Wire the contact to input DE1, DE2 or DE3 on extension module EA1 in the boiler electrical junction box. Power the relay and thermostat as the manufacturer instructs. When the thermostat contact closes, burner operation is load-dependent and the supply water heats to the value in coding address 9b (General group). The supply temperature is still limited by the electronic supply temperature maximum. Live contacts cause short circuits or phase failure, so the connection must be potential-free. For thermostat-only room control, the standard and reduced room temperature set points can be set to 37 ºF (3 ºC) to reduce cycling. Example relays named in the manual are Taco SR501 and Honeywell RA889A-1001, both field supplied.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

How to fix connecting a 24 vac thermostat through a switching relay: step by step

  1. Connect the normally open dry contact (T-T) of the switching relay to DE1, DE2 or DE3 on EA1.
  2. Connect the relay to the thermostat and power supply per manufacturer instructions.
  3. Set coding 3A, 3B or 3C in the General group to 2.
  4. Set coding 9b to the required maximum supply water temperature.
  5. Keep the contact potential-free.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.