Viessmann Boiler: Connecting 120V external pumps
Connecting 120V external pumps on a Viessmann boiler: Pump wiring depends on the pump's electrical draw and voltage. Larger pumps and non-120V pumps need a field-supplied contactor or relay.
Applies to: Vitotronic 200-H HK1B, external pump connections
How to fix connecting 120v external pumps: step by step
- For 120V pumps drawing more than 2 FLA, use a field-supplied contactor or relay rated 120VAC 1A.
- For 208/460/575V 3-phase pumps, use a field-supplied contactor or relay rated 120VAC 1A.
- For 240V pumps, use a field-supplied contactor or relay rated 120VAC 1A.
- Feed the contactor from a power supply with disconnect and protection.
- For 120V pumps drawing less than 2 FLA, wire the pump directly to the DIN rail.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.