Viessmann Boiler: Connect the gateway to the boiler control and network
Connect the gateway to the boiler control and network on a Viessmann boiler: The gateway links to the boiler control over a supplied CAT-5 cable and to the BMS over BACnet IP. The LON communication card must be fitted in the control first.
Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B, Vitotronic 200 HO1, Vitodens 200 B2HA
How to fix connect the gateway to the boiler control and network: step by step
- Refer to the manual for the specific boiler control and confirm the LON communication card is installed.
- Plug the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket on the control.
- Plug the other end of the cable into the RJ45 socket inside the gateway.
- Plug the BACnet IP RJ45 cable into the gateway for the network connection.
- For the 120VAC unit, plug the power cord into the gateway.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 515 BACnet IP Type B manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.