Viessmann Boiler: Connect the control unit to the Viessmann 2-wire BUS system
Connect the control unit to the Viessmann 2-wire BUS system on a Viessmann boiler: Set the BUS address and matching coding when the control shares a system with a boiler control or other Vitotronic.
Applies to: Vitotronic 200-H on Viessmann 2-wire BUS
How to fix connect the control unit to the viessmann 2-wire bus system: step by step
- Plug in the Viessmann 2-wire BUS communication module (accessory; see parts list).
- Set the rotary dial on the communication module to a value between 4 and C that matches the system version.
- Do not set the rotary dial to the same value as another control unit.
- On a wall-mounted boiler with an actuator kit (Part No. 7133 392) for one mixing valve controller, the default rotary dial position is 4. Do not duplicate 4 when adding a second Vitotronic 200-H.
- With a boiler control for wall-mounted boilers or a Dekamatik system, adjust the differential temperature at that control.
- On the Vitotronic 200-H, set coding 9F to 0.
- If the outdoor temperature comes from a sensor already connected, set coding 97 to 1.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.