Viessmann Boiler: Connect the control unit to the LON system
Connect the control unit to the LON system on a Viessmann boiler: Set up the LON participant number and check the LON data exchange on a multi-unit system.
Applies to: Vitotronic 200-H on a LON system
How to fix connect the control unit to the lon system: step by step
- Plug in the LON communication module (accessory; see parts list).
- Set the LON participant number in coding 1 using coding address 77.
- Make sure no LON participant number is used twice.
- Allow several minutes for LON data transfer.
- Update the user list at the control unit that is set as fault manager, and run the participant check.
- Refer to the service instructions of that control unit for details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H installation and service instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.