Viessmann Boiler: Connect low water cut-off device (VD2/VD2A/CT3)
Connect low water cut-off device (VD2/VD2A/CT3) on a Viessmann boiler: Wire the external LWCO into the control terminals. The factory jumper between 12 and 15 must come out first.
Applies to: VD2, VD2A and CT3 controls
How to fix connect low water cut-off device (vd2/vd2a/ct3): step by step
- Disconnect power before working on the wiring.
- Remove the jumper between terminals 12 and 15.
- Connect the LWCO as shown in the diagram.
- Use the power supply for accessories (aBH) and the external equipment connection (aBÖ) as labelled.
- Refer to the LWCO device manual for interconnection details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 73. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.