Viessmann Boiler: Connect combustion air damper through common interface

Updated · by Aurora Star Tech Inc.

Connect combustion air damper through common interface on a Viessmann boiler: Wire the shared damper on a multiple boiler system, with a field-supplied relay.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Multiple boiler system, shared damper

How to fix connect combustion air damper through common interface: step by step

  1. Disconnect power to the control and burner.
  2. Wire the damper motor (120 VAC, 5 FLA max.) to the common combustion air device interface.
  3. Wire the proving switch (120 VAC rated) and the 120 VAC supply as shown.
  4. Add the field-supplied relay as shown in the diagram.
  5. Provide disconnect means and overcurrent protection as local codes require.
  6. Select the fuse using the damper manual's current rating.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 44. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.