Viessmann Boiler: Connect combustion air damper through common interface
Connect combustion air damper through common interface on a Viessmann boiler: Wire the shared damper on a multiple boiler system, with a field-supplied relay.
Applies to: Multiple boiler system, shared damper
How to fix connect combustion air damper through common interface: step by step
- Disconnect power to the control and burner.
- Wire the damper motor (120 VAC, 5 FLA max.) to the common combustion air device interface.
- Wire the proving switch (120 VAC rated) and the 120 VAC supply as shown.
- Add the field-supplied relay as shown in the diagram.
- Provide disconnect means and overcurrent protection as local codes require.
- Select the fuse using the damper manual's current rating.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.