Viessmann Boiler: Connect CombiPLUS flex piping to the boiler
Connect CombiPLUS flex piping to the boiler on a Viessmann boiler: Connect the flex pipes between the boiler bottom tees and the CombiPLUS extension fittings.
Applies to: Vitodens 100-W WB1B with CombiPLUS, 7 in flex pipe
How to fix connect combiplus flex piping to the boiler: step by step
- Install the adaptors to the tees at the bottom of the boiler, then attach the flex pipes to the adaptors.
- Bend the flex pipes to line up with the CombiPLUS extension fittings, because of the offset between boiler and CombiPLUS.
- Slide the CombiPLUS up and attach the flex pipes to its extension fittings.
- Tighten the two lag bolts in the mounting bracket slots, install the washers, and tighten the upper mounting bolts into the wall anchors.
- Tighten the flex pipe hex nuts by hand plus a partial turn with a wrench. This is a gasketed joint, so do not overtighten.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W WB1B installation and service instructions, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.