Viessmann Boiler: Connect boiler return mixing or isolation/modulating valve actuator (CM2)
Connect boiler return mixing or isolation/modulating valve actuator (CM2) on a Viessmann boiler: Use a 120 V or 24 V valve adaptor. Valve run time is set by coding 40 between 5 and 199 seconds.
Applies to: CM2
How to fix connect boiler return mixing or isolation/modulating valve actuator (cm2): step by step
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Plug the gS plug into socket gS on the control.
- Secure the cable with a tie.
- Connect the black adaptor wire to the 120V L out DIN rail connection, terminals 10, 11 or 12.
- Wire the valve actuator to the adaptor terminals as shown in the figures.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100, GC1 installation manual, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.