Viessmann Boiler: Connect boiler activation contact (plug aVH, terminals 2 and 3)
Connect boiler activation contact (plug aVH, terminals 2 and 3) on a Viessmann boiler: Dry contact that controls preheat, isolation valve and modulation on external modulation setups.
Applies to: VD2/VD2A and CT3 with external modulation controller
How to fix connect boiler activation contact (plug avh, terminals 2 and 3): step by step
- Disconnect power before wiring.
- Connect a dry contact to terminals 2 and 3 of plug aVH.
- With contact closed, preheat runs first for follow-up boilers (coding 2b). After preheat, minimum temperature holds and burner stages or modulation can be switched externally. Setpoint is chosen by coding 9b.
- With contact open, the isolation valve closes after about 5 minutes (coding 2C). External override of burner stages is not possible and no minimum temperature is held.
- On multi-boiler systems the lead boiler contact must be constantly closed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 41, 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.