Updated · by Aurora Star Tech Inc.

Connect a 24 VAC room thermostat through a switching relay on a Viessmann boiler: A normally open dry contact from a switching relay (T-T) connects to the EA1 module. When the thermostat contact closes, burner operation is load-dependent and the supply water heats to the value in coding address 9b. The contact must be potential-free, since live contacts cause short circuits or phase failure.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1

Common causes of connect a 24 vac room thermostat through a switching relay

  • Live voltage on the thermostat contact causes short circuits or phase failure

How to fix connect a 24 vac room thermostat through a switching relay: step by step

  1. Connect the normally open dry contact of the switching relay (T-T) to terminal DE1, DE2 or DE3 of EA1 in the boiler electrical junction box.
  2. Connect the switching relay to the thermostat and power supply per the manufacturer's instructions.
  3. Set coding address 3A, 3B or 3C in the General group to 2.
  4. Confirm the contact is potential-free.
  5. If only a field-supplied thermostat controls room temperature, the standard and reduced room set points may be set to 37 ºF (3 ºC) to reduce boiler cycling.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 34. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.