Viessmann Boiler: Condensate drain installation and neutralization
Condensate drain installation and neutralization on a Viessmann boiler: Condensate from the boiler and flue pipe is acidic (pH 3 to 4). It must go to the drain through a trap, and a neutralizer is used where local code requires it.
Applies to: B2HB 19 to 57, 68 to 199
How to fix condensate drain installation and neutralization: step by step
- Run the condensate drain pipe with a continuous fall toward the drain.
- Use corrosion-resistant materials only, such as braided hose. Do not use galvanized pipe or copper-containing fittings.
- Install a trap in the drain to stop flue gas leakage, and make the outlet visible with a stench trap.
- If the boiler condensate outlet is below the drain, install a condensate pump.
- If a neutralizer is used, vent the pipe between the siphon trap and the neutralizer.
- Check the neutralizer granulate level several times in the first year to set the refill interval. Treated water should be above pH 6.5 when discharged.
- Confirm local waterworks and waste water rules before installing the neutralizer.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.