Viessmann Boiler: Combustion air duct requirements
Combustion air duct requirements on a Viessmann boiler: Outdoor air ducts must meet these size rules. Sizing for openings is in the combustion air opening table.
Applies to: VR1 22 to 33, 91 to 140
How to fix combustion air duct requirements: step by step
- Make the duct cross-sectional area along its full length at least equal to the free area of the openings it connects.
- Keep the minimum duct dimension at 3 in (76 mm) at any section.
- Keep the outside air intake at least 1 ft (0.3 m) above the expected snow level.
- If a damper is in a combustion air opening, interlock it so no burner can start until the damper is fully open.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.