Viessmann Boiler: Combustion air device connection (VD2/VD2A/CT3)
Combustion air device connection (VD2/VD2A/CT3) on a Viessmann boiler: Connect a combustion air blower through the combustion air device adaptor.
Applies to: VD2, VD2A and CT3 combustion air blower
How to fix combustion air device connection (vd2/vd2a/ct3): step by step
- Disconnect power to the control and burners.
- Mount the combustion air device adaptor (part no. 7134 563) on the DIN rail inside the connection enclosure, following the adaptor's manual.
- Remove the jumper between terminals 16 and 17.
- Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
- Wire the blower to the adaptor as shown in the diagram.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.