Viessmann Boiler: Combustion air device adaptor wiring (VD2/VD2A/CT3)

Updated · by Aurora Star Tech Inc.

Combustion air device adaptor wiring (VD2/VD2A/CT3) on a Viessmann boiler: Connecting the combustion air blower through the adaptor to the control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 VD2/VD2A/CT3

How to fix combustion air device adaptor wiring (vd2/vd2a/ct3): step by step

  1. Disconnect power to the control and burners.
  2. Mount the combustion air device adaptor (part 7134 563) on the DIN rail inside the connection enclosure, following the adaptor manual.
  3. Remove the jumper between terminals 16 and 17.
  4. Connect BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
  5. Wire the blower (120 VAC, max 5 FLA, AWG 14) to the adaptor as shown. The proving switch must be normally open and rated 120 VAC.
  6. Connect 120 VAC power with disconnect and overcurrent protection as required by local codes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

GC1KW10B

Source: Viessmann Vitotronic 100 GC1 installation manual, p. 66. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.