Viessmann Boiler: Combustion air damper with relay and end switch
Combustion air damper with relay and end switch on a Viessmann boiler: Wiring a combustion air damper through a field relay and end switch.
Applies to: Single boiler combustion air damper
How to fix combustion air damper with relay and end switch: step by step
- Disconnect power to the control and burner.
- Wire the 120 VAC relay coil (field supplied) to the damper circuit as shown.
- Wire the damper end switch (120 VAC) to the normally open terminal on the adaptor board.
- Connect power (120 VAC) with disconnect and overcurrent protection as required by local codes.
- Spring return dampers do not need the field relay. Follow the damper manual for installation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 installation manual, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.