Coco OT module overview and wiring on a Viessmann boiler: The Coco OT module translates the Versatronik 200 CAN signal to OpenTherm for each OT-enabled boiler. Each boiler needs its own Coco OT module, and the control ships with two. Extra modules must be ordered for more than two OT boilers. Modules can be mounted near the control or near the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Coco OT module with Versatronik 200 System Control

How to fix coco ot module overview and wiring: step by step

  1. Wire the Versatronik 200 to the Coco OT with 4-conductor cable (power and CAN).
  2. Wire the Coco OT to the boiler with 2-conductor cable (OpenTherm).
  3. Make sure CAN H and CAN L are not reversed, or communication faults can occur.
  4. Daisy-chain the modules from the previous Coco OT module.
  5. Plug the 4-pole connector into the Versatronik 200 only after all interconnections are complete.
  6. Set the DIP switches on each Coco OT for its boiler number (1 to 8).
  7. Check the boiler-specific manual for OT connections inside the boiler.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Versatronik 200 installation and operating manual, p. 16-17. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.