Viessmann Boiler: Cleaning the burners
Cleaning the burners on a Viessmann boiler: Clean the fan and burner tube from the gas valve side, then reassemble and check for gas leaks.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Common causes of cleaning the burners
- Dirty fan housing or impeller
- Debris in burner tube
How to fix cleaning the burners: step by step
- Close the central gas shut-off valve.
- Disconnect the Venturi mixing tube from the fan.
- Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if fitted.
- Detach connector pipes a-Ö and a-ÖA from the fan and remove the fan.
- Clean the fan housing and impeller with compressed air.
- Vacuum the burner tube inside and out if needed.
- Reassemble in reverse order.
- Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
- Check screws and the fan-to-burner plate gasket for gas leaks.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.