Viessmann Boiler: Cleaning the burner fan, Venturi tube and burner tube
Cleaning the burner fan, Venturi tube and burner tube on a Viessmann boiler: Cleaning the fan and burner assembly and checking for gas leaks after reassembly.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner fan and Venturi
Common causes of cleaning the burner fan, venturi tube and burner tube
- Dirt on the fan impeller or housing.
- Gasket between fan housing and burner plate damaged.
How to fix cleaning the burner fan, venturi tube and burner tube: step by step
- Close the central gas shut-off valve before any burner work.
- Disconnect the Venturi mixing tube from the fan.
- Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if needed.
- Detach the connector pipes from the fan and remove the fan.
- Clean the fan housing and impeller with compressed air.
- Vacuum the burner tube inside and out if necessary.
- Reassemble in reverse order and fit the gasket between fan housing and burner plate in the correct position. Replace it if damaged.
- Check for gas leakage at the screws and at the gasket between the fan housing and the burner plate.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.