Viessmann Boiler: Clean heat exchanger, flue gas collar and chimney connection
Clean heat exchanger, flue gas collar and chimney connection on a Viessmann boiler: Remove combustion residue from the heat exchanger, combustion chamber, flue collar and chimney connection. Check the gaskets and insulation at the same time.
Applies to: Vitorond 200 VD2A boilers
Common causes of clean heat exchanger, flue gas collar and chimney connection
- Combustion residue builds up in the flue passages over time.
How to fix clean heat exchanger, flue gas collar and chimney connection: step by step
- Clean flue gas passages and the combustion chamber with the supplied brush.
- Clean tight spaces between the ribs with the smaller brush.
- Vacuum out combustion residue.
- Remove residue from the chimney connection and flue collar through the clean-out openings at the rear of the boiler.
- Check all gaskets and sealant ropes and replace any that are worn.
- Check the insulation of the combustion chamber door and replace it if worn.
- On VD2A-125 to VD2A-195, push the turbulators fully into the second flue passages.
- Tighten the combustion chamber door bolts in a cross pattern.
- If a gas power burner is used, reconnect the gas train and run leak detection.
- Refit the clean-out covers.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A service instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.