Viessmann Boiler: Clean condensate trap and check condensate drain
Clean condensate trap and check condensate drain on a Viessmann boiler: If condensate does not drain freely it builds up in the bottom of the boiler and causes a burner shut-down (fault message). Keep the drain and trap clear.
Applies to: Vitodens 200-W B2HB 19 to 125 boiler
Common causes of clean condensate trap and check condensate drain
- Blocked condensate trap or drain
- Condensate not draining freely
- Another appliance drain connected to the condensate line
How to fix clean condensate trap and check condensate drain: step by step
- Remove the retaining clip from the condensate trap and set it aside.
- Disconnect the flexible discharge tubing from the trap.
- Remove the condensate trap from the boiler.
- Clean out debris and refill the trap with water.
- Reinstall the trap and secure it with the retaining clip.
- Reconnect the flexible discharge tubing.
- Do not connect other drains, such as a water softener backwash, to the Vitodens condensate drain.
- Make sure the pipe is vented between the trap and the neutralization unit, if fitted.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.