Viessmann Boiler: Clean combustion chamber and heat exchanger surface

Updated · by Aurora Star Tech Inc.

Clean combustion chamber and heat exchanger surface on a Viessmann boiler: Remove debris and sediment from the combustion chamber and stainless steel heat exchanger. Discoloration of the heat exchanger is normal and does not affect function or life.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

Common causes of clean combustion chamber and heat exchanger surface

  • Sediment buildup on heat exchanger
  • Debris in combustion chamber
  • Debris plugging heat exchanger coil gaps

How to fix clean combustion chamber and heat exchanger surface: step by step

  1. Remove the burner assembly and reinstall it when service is complete, per the burner instructions on page 23.
  2. Vacuum loose debris out of the combustion chamber.
  3. Rinse embedded sediment off the stainless steel heat exchanger with water or an approved cleaning agent. Follow the agent's safety and application instructions and wear protective equipment.
  4. Do not use a metal wire brush or mechanically driven brush. Keep the refractory dry.
  5. If heat exchanger coil gaps are plugged, remove debris with the Viessmann tool made for this purpose, without scratching the surface.
  6. Flush the combustion chamber with water until it runs clear through the condensate trap.
  7. Clean out debris from the condensate trap and reinstall it.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.