Viessmann Boiler: Circulation pump connection
Circulation pump connection on a Viessmann boiler: Pumps can be hard-wired to the Power Pump Module terminal strip, or Viessmann pre-wired pumps can be plugged into the Rast-5 terminals. Only Viessmann pre-wired pumps may be used with the plug-in terminals.
Applies to: Boiler circuit pump, DHW production pump, DHW recirculation pump, Vitotronic 300
How to fix circulation pump connection: step by step
- Use only Viessmann pre-wired (plug-in) circulating pumps if the plug-in terminals are used.
- Insert the supplied strain relief through the Power Pump Module knock-out and fasten it with the nut.
- Connect the Rast-5 connector to the matching plug-in terminal on the Power Pump Module.
- If pre-wired pumps are used, do not also connect a pump to the matching hard-wired terminal.
- For underfloor heating, also install an adjustable high limit. Put the fixed high limit in the heating supply pipe after the mixing valve and the heating circuit pump.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 installation instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.