Viessmann Boiler: Choose and prepare the boiler room
Choose and prepare the boiler room on a Viessmann boiler: Boiler room air must be clean, unrestricted and never under negative pressure. Exhaust, attic or dryer fans can pull air faster than the structure can supply it for combustion.
Applies to: VR1 22 to 33, 91 to 140
How to fix choose and prepare the boiler room: step by step
- Place the boiler near an outside wall so fresh air can be ducted to it.
- Do not use exhaust fans in the boiler room or install the boiler near refrigeration equipment.
- Keep the boiler away from stored chemicals and aggressive vapors such as bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene, and away from high dust or humidity.
- Set the boiler on floor able to carry its filled weight, without blocking combustion or ventilation air circulation.
- Never cover the boiler or the combustion air opening, and never store debris near it.
- Place the boiler in a heated indoor space near a floor drain and as close to the chimney or vent as possible.
- Use a concrete foundation if the floor may flood, is not level, or the boiler is in a residential garage. In a garage, raise the burner at least 18 in (457 mm) above the floor.
- Check local authority and gas utility requirements for combustion air.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.