Chimney and venting general requirements on a Viessmann boiler: All combustion products must go outdoors through a chimney sized and insulated for this boiler's low flue gas temperatures. Oversized or uninsulated chimneys cause corrosive condensation. The VD2A is not approved for side wall venting.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 200 VD2 320 to 1080; VD2A not for side wall venting

Common causes of chimney and venting general requirements

  • Chimney too large or not insulated, so flue gas cools too fast and condenses
  • Vent connection not insulated

How to fix chimney and venting general requirements: step by step

  1. Size the chimney for the boiler model and input. If a calculated diameter falls between two sizes, choose the larger one.
  2. Insulate the chimney connection from the vent pipe collar to the chimney.
  3. Do not assume the vent collar diameter sets the chimney size.
  4. Install a barometric draft regulator in the chimney or vent.
  5. Never run the boiler without an installed venting system.
  6. Follow local and national codes. Canada: CAN/CSA B149.1 or .2 for gas, CSA B-139 for oil. USA: NFPA 54 venting provisions and ANSI Z223.1 for gas, NFPA 31 for oil.
  7. Do not stand on the top panel when installing or insulating overhead piping or venting.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.