Viessmann Boiler: Checking the outdoor temperature sensor
Checking the outdoor temperature sensor on a Viessmann boiler: Resistance check of the outdoor sensor and cable.
Applies to: Outdoor temperature sensor
How to fix checking the outdoor temperature sensor: step by step
- Disconnect one lead of the sensor cable.
- Measure the sensor resistance at the end of both leads.
- If readings strongly deviate from the curve values, repeat the test and compare with the actual temperature (scan on p. 21).
- Replace the cable or the outdoor temperature sensor depending on the result.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H Installation and Service Instructions, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.