Viessmann Boiler: Checking the flue gas flapper
Checking the flue gas flapper on a Viessmann boiler: Back flue gas flapper in the burner mixing shaft. Check the damper and gasket for dirt or damage.
Applies to: B1HE/KE 85/120 and 150/199
How to fix checking the flue gas flapper: step by step
- Undo the 2 screws and remove the fan.
- Remove the flue gas flapper.
- Check the damper and gasket for dirt and damage, and replace if needed.
- Refit the flapper with the correct installation position.
- Refit the fan and secure with 2 screws to 35 lb.in (4.0 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.