Viessmann Boiler: Checking the fixed high limit (STB test)
Checking the fixed high limit (STB test) on a Viessmann boiler: Test the fixed high limit (STB) on the Vitotronic 100 with the TÜV test button held. The adjustable high limit is bypassed during the test, so the burner runs until the STB cuts it off.
Applies to: Vitotronic 100, GC1
How to fix checking the fixed high limit (stb test): step by step
- Make sure a minimum flow is present. Boiler flow should be about 10% of rated output.
- Reduce the heat demand as far as possible.
- Hold the TÜV test button down. The adjustable high limit R is now bypassed.
- Let the burner run until boiler water reaches the safety temperature and the fixed high limit (STB) switches off.
- Release the TÜV button. The display shows fault D4.
- Wait until boiler water is 15 to 20 °C (25 to 35 °F) below the set safety temperature.
- Press button E to reset the fixed high limit. Fault D4 clears from the display.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.