Viessmann Boiler: Checking the DHW tank, supply and room temperature sensors
Checking the DHW tank, supply and room temperature sensors on a Viessmann boiler: Test the NTC 10 kΩ sensors used for DHW tank, supply and room temperature. Measure across the plug terminals 1 and 2.
Applies to: DHW tank, supply and room sensors, Viessmann NTC 10 kΩ (blue)
Common causes of checking the dhw tank, supply and room temperature sensors
- Results very different from the curve point to the sensor or the lead
How to fix checking the dhw tank, supply and room temperature sensors: step by step
- Pull the sensor plug.
- Measure the resistance across plug terminals 1 and 2 and compare it with the curve.
- If the result is very different, disconnect the wires from the sensor and repeat the test on the sensor alone.
- Depending on the result, replace the lead or the sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.