Viessmann Boiler: Checking the condensate drain and cleaning the siphon trap
Checking the condensate drain and cleaning the siphon trap on a Viessmann boiler: A dry or unfilled siphon trap lets flue gas escape. Route the drain hose with no bends and a constant fall.
Applies to: Condensate drain and siphon trap
Common causes of checking the condensate drain and cleaning the siphon trap
- Debris in the siphon trap
- Trap not filled or not seated
How to fix checking the condensate drain and cleaning the siphon trap: step by step
- Cover electronic components with watertight material.
- Move the bracket with the programming unit to the maintenance position.
- Remove the supply hose.
- Pull the siphon trap up out of the drain hose, keeping it level so condensate does not spill.
- Clean the siphon trap.
- Fill the siphon trap with water and refit it on the drain hose.
- Refit the supply hose and make sure the clip is sealed and closed.
- Check connections for leaks and confirm the trap is seated correctly.
- Remove any condensate that escaped before commissioning. Do not start the boiler until the trap is filled.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.