Viessmann Boiler: Checking the boiler, DHW tank, supply or low-loss header temperature sensors
Checking the boiler, DHW tank, supply or low-loss header temperature sensors on a Viessmann boiler: Warning: the boiler temperature sensor is in the heating water (scalding risk), so drain the boiler before replacing it. Sensor type is NTC 10 kΩ. Only one supply or low-loss header temperature sensor may be used.
Applies to: Vitodens 222-F B2TB
How to fix checking the boiler, dhw tank, supply or low-loss header temperature sensors: step by step
- Boiler sensor: remove the lead to boiler water temperature sensor A and check the resistance.
- DHW tank sensor: pull plug from the cable harness at the control unit and check the resistance.
- Supply or low-loss header sensor: pull plug X3 from the control unit and check the resistance across terminals X3.4 and X3.5.
- Compare the actual values with the curve.
- Replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F B2TB service instructions, p. 83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.