Viessmann Boiler: Checking and cleaning the burner tube
Checking and cleaning the burner tube on a Viessmann boiler: Service procedure for inspecting and cleaning the burner tube and burner gauze assembly. Work only on a cold system with the gas shut-off closed.
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
How to fix checking and cleaning the burner tube: step by step
- Dismantle the burner (see the burner dismantling section, p. 70).
- Undo the 6 screws from the insulation ring. Torque on reinstall: 13 lb.in (1.5 Nm).
- Remove the insulation ring.
- Unscrew the burner gauze assembly. Vacuum it or replace it. Torque on reinstall: 7.5 lb.ft (10 Nm).
- Replace all gaskets. Reassemble the burner tube and burner in reverse order. Torque: 7.5 lb.ft (10 Nm).
- Keep insulation fibres away from the burner tube and out of the combustion chamber when fitting a new tube.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.