Viessmann Boiler: Checking and cleaning the burner tube and gauze
Checking and cleaning the burner tube and gauze on a Viessmann boiler: Cleaning or replacing the burner gauze and inspecting the insulation ring.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner tube
Common causes of checking and cleaning the burner tube and gauze
- Contamination of the burner tube can cause malfunctions.
- Scratches in the combustion chamber can cause corrosion.
How to fix checking and cleaning the burner tube and gauze: step by step
- Dismantle the burner first (see page 69).
- Undo the 6 screws from the insulation ring (torque 13 lb.in / 1.5 Nm on refit) and remove the ring.
- Unscrew the burner gauze assembly. Vacuum it or replace it (torque 7.5 lb.ft / 10 Nm on refit).
- Replace all gaskets and reassemble in reverse order (torque 7.5 lb.ft / 10 Nm).
- Keep the combustion chamber free of insulation fibres and do not let tools fall in.
- Close the gas shut-off valve before working and only work on the burner when the system is cold.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.