Viessmann Boiler: Check water fill pressure and safety devices
Check water fill pressure and safety devices on a Viessmann boiler: Perform these checks on a cold system. A low fill pressure usually means water loss from a leak, and all leaks must be fixed.
Applies to: All VD2 sizes 320 to 1080
Common causes of check water fill pressure and safety devices
- Water loss through leakage, shown by low fill pressure
How to fix check water fill pressure and safety devices: step by step
- Check the pressure gauge, air vent and pressure relief valve.
- Confirm the pressure relief valve does not leak and operates to its manufacturer's data.
- Check system water pressure in the diaphragm expansion tank, low water cut-offs, pumps and pressure relief valve.
- Confirm the usual cold fill pressure is 12 to 15 psig.
- Flush float-type low water cut-offs if used.
- Refer to the auto fill valve instructions and local backflow rules.
- Lubricate oil-lubricated pumps if used.
- Check motorized zone valves per their maintenance instructions.
- On an older non-diaphragm tank, confirm the correct water level (about one-half full).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.