Viessmann Boiler: Check three-phase burner motor rotation
Check three-phase burner motor rotation on a Viessmann boiler: Caution: a motor running backwards is a known risk on three-phase burners. Check rotation at commissioning and correct it at the burner terminals, never on the control.
Applies to: Three-phase burners, VD2/VD2A/CT3
How to fix check three-phase burner motor rotation: step by step
- Power up the burner and observe motor rotation.
- If rotation does not match the burner direction, disconnect all power first.
- Reverse the BK1 and BK2 wires on the burner terminals.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More commissioning tips for boiler
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.