Viessmann Boiler: Check the supply temperature sensor (strap-on or immersion)
Check the supply temperature sensor (strap-on or immersion) on a Viessmann boiler: The supply sensor plugs into socket ? on the control unit. Check it by resistance against the current supply temperature.
Applies to: Common supply temperature sensor
Common causes of check the supply temperature sensor (strap-on or immersion)
- Sensor reading differs significantly from actual temperature
How to fix check the supply temperature sensor (strap-on or immersion): step by step
- Disconnect plug ? in the terminal compartment.
- Measure the sensor resistance at terminal 2 of the plug.
- Compare the reading with the current temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 79. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.