Viessmann Boiler: Check the return temperature sensor
Check the return temperature sensor on a Viessmann boiler: Use this to check a strap-on or immersion return temperature sensor against the actual temperature.
Applies to: Return temperature sensor, strap-on or immersion
How to fix check the return temperature sensor: step by step
- Disconnect the sensor from the terminals.
- Measure the sensor resistance between terminals 1 and 2 of the plug.
- Compare the reading with the resistance table for the current return temperature.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 100/300-K installation and service instructions, p. 63. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.