Viessmann Boiler: Check the flue gas temperature sensor
Check the flue gas temperature sensor on a Viessmann boiler: Applies to VD2, VD2A and CT3 only. The sensor plugs into socket 15 on the boiler control.
Applies to: Flue gas temperature sensor 7450 630 (VD2, VD2A, CT3)
How to fix check the flue gas temperature sensor: step by step
- Disconnect plug aG in the terminal compartment of the boiler control.
- Measure resistance at terminals 1 and 2 of the plug.
- Compare with the table: 160 °C / 320 °F about 800, 200 °C / 392 °F about 880.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 104. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.