Viessmann Boiler: Check the flue gas temperature sensor (VD2/VD2A/CT3 only)
Check the flue gas temperature sensor (VD2/VD2A/CT3 only) on a Viessmann boiler: Monitors flue gas temperature against a selected limit. Plugs into socket 15.
Applies to: Flue gas temperature sensor, socket 15, VD2/VD2A/CT3 only
How to fix check the flue gas temperature sensor (vd2/vd2a/ct3 only): step by step
- Disconnect plug aG in the terminal compartment.
- Measure resistance at terminals 1 and 2 of the plug.
- Compare the reading with the actual flue gas temperature using the resistance table.
- If the value differs significantly, check installation and replace the sensor if needed.
- Plug the sensor into socket 15 on the boiler control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 Installation and Service Instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.