Viessmann Boiler: Check the flue gas flapper
Check the flue gas flapper on a Viessmann boiler: Inspect the flapper behind the fan.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix check the flue gas flapper: step by step
- Undo three screws and remove fan A.
- Remove the flue gas flapper B.
- Check the flapper and gasket for dirt and damage. Replace as needed.
- Refit the flapper and the fan with three screws. Torque 2.2 lb.ft. (3.0 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.